Educational Webinars, On Demand
We have a number of educational webinars for you to view on demand
 Find out more
Need advice? Speak to our sales experts: +1-813-886-2775
For tech support please contact us

All of my Insulation Resistance test values are around “0.05MΩ or less”?

This is normally an indication that Earth and Neutral are connected together in the installation. Readings should be greater than 1MΩ for an Earthed system, or 2MΩ for Class 2 or “floating” systems. Ideally this reading should be as high as possible. PV150 can read up to 19.99MΩ, and the PV200/210 up to 199.99MΩ. A good result would be “>19.99MΩ” on the PV150, and “>199.99MΩ” on the PV200/210.

Still need help? Ask us.


Stay in the know
Sign up to our mailing list today to stay up to date with the latest industry news and information from Seaward Group USA.

I'd like to talk to a sales advisor

Our team of sales advisors are on hand to help you with any queries you have about our products.